TS690 & TS690IDIntruder Alarm Control PanelsInstallation & ProgrammingManual_~Engineers menu 2Select option :-_~OPEN_~Engineers menu 2Select o
Control Panel PCB Layout10System Installation TS690 & TS690ID Installation ManualPRINTERREMOTE KEYPADJP3DIGI-MODEMPLUG ON DIGI MODEMJP4FACTORYRESE
Connection Terminals & IndicatorsConnection terminals on the TS690 / TS690ID aredescribed as ether “Safety Extra-Low Voltage”(SELV) circuits or “T
Mains ConnectionThe mains supply is connected to a 3 way “EuroType” fused terminal block, which is fitted with a315mA fuse. All electrical connections
8 Network Connections & O/P.Terminals A to E are used to connect theremote keypad to the control panelnetwork. The O/P terminal is theprogrammable
5. Set the “ENT KEY DISABLE” jumper link to therequired position.6. Set the “WARD SOUNDER CONTROL” jumper linkto the required position.7. Finally clip
4. Connect “Remote Network” cables anddetection circuit cables to the appropriateterminals, see Figure 105. Set the I/D selector jumper link to the re
Wiring ID BiscuitsEach ID biscuit is identified by its own number, 01to 30 and contains its own internal sensor which iscontinuously monitored by the
Wiring a Biscuit to a Panic ButtonThe figure below shows typical wiring configurationfor a standard panic button.Wiring a Biscuit to a Smoke DetectorT
Extension LoudspeakersUp to two extension loudspeakers can beconnected across the [SPK+] and [H/O-] terminalson the control panel PCB. The volume for
ApplicationThe DC6 digital communicator/modem is suitablefor connection to the following types of telephoneline:lDirect exchange lines (PSTN) supporti
ContentsOverviewIntroduction . . . . . . . . . . . . . . . . . . . . . . . . . 4Control Panel . . . . . . . . . . . . . . . . . . . . . . . . 4Remote
InstallationFor your safety, installation of the DC6MUST be carried out in the sequenceshown below:1. Ensure that all power is removed from thesystem
Connecting a PrinterThe TS690 and TS690ID supports two type ofprinters, the CPA6 printer (no longer available) andany standard RS232 printer. When usi
Pre Power-Up ChecksOnce the system is installed, but prior topowering-up, give the system one final check toensure that:1. The wiring conforms to the
3. With the ID loop still disconnected from thecontrol panel, use a DVM to measure theresistance between the following cores andterminals:(a) ID + cor
NVM Defaults24System Installation TS690 & TS690ID Installation ManualSection Option DefaultUser CodesUser 00 Engineer 1234User 01 Master 5678Panel
Engineer’s Menu 1IntroductionEngineers menu 1 is the first of two engineersmenus, which is selected when the engineer’spasscode is entered. The engine
Panel Outputs [1.1]Outputs 1-3 on the control panel and remotekeypad outputs 5-8 can be programmed to anyof the output types shown on pages 26 to 29.D
No Type/Description004 Walk TestActivates when the "Walk Test" option isselected and deactivates when the "Walk Test"option is fin
No Type/Description032 Duress AlarmActivates when a duress passcode is enteredand deactivates when the duress alarm isreset.033 System Part SetActivat
and the circuit remains active until the end ofthe confirmation time then the control panelomits the active zone and triggers the ActiveOmit output. T
Add/Clear ID Devices (TS690ID) . . . . . . . . . . 39Clear & Relearn ID Devices . . . . . . . . . . . 39Add ID Devices. . . . . . . . . . . . . .
[7] Inverted - Inverts the operation of thekeyswitch.If the “Keyswitch” is not assigned to any of theabove options, the circuit becomes a“Monitored” c
System Timers [1.5]The system timers are as follows:00 Abort DelayThis timer sets the period in which the alarmsignal may be aborted following an alar
06 Bell DurationThis controls the duration of the externalbell/sounder. If the timer is set to 199 the belloutput is continuous. This timer has a work
19 Test CallIf the system is fitted with a DC6, it is possible forthe control panel to make the DC6 send atimed test call to the central station. The
To set the system the user first enters theiraccess code at a keypad or operates akeyswitch. The control unit starts the exit tone.Note that the exit
Remote Reset Algorithm [1.8]When the system is programmed for “EngineerReset” the requirement to send an engineer to sitecan be overridden by the user
10 Tamp user resetWhen programmed as “Yes", tamper alarmscan be reset by the user. When programmedas ”No", tamper alarms can only be reset b
25 Answer Phone DefWhen programmed as “Yes”, the plug-ondigi-modem will only answer incoming callsafter a second attempt. When programmedas “No”, the
34 Entry Keypad LockWhen programmed as “Yes” then users cannotunset the system from a keypad during entry.Program this option as “Yes” if you are inst
Go to User Menu 1 [1.0]This option allows the engineer to access “Usermenu 1", the flowchart below shows the optionswithin ”User menu 1", fo
OverviewIntroductionThe TS690 range of alarm control systems havebeen designed to suit small to medium installationsites. The TS690 system can monitor
View Location Text (LCD Only) [1.B]This option allows the engineer to view the panellocation text. The text message is programmed in"Engineers me
Engineer's Menu 2IntroductionEngineer's menu 2 is selected by pressing the [ENT]key whilst Engineer's menu 1 is selected. Eachmenu opti
View Circuits [2.1]Each detection circuit may be viewed toascertain its status. The circuit status conditionsand resistance are shown below:Status Res
Change Passcode [2.4]This option allows the engineer to change theirpasscode. The default passcode is 1234 but theinstallation engineer should change
Configure Part Sets [2.8]The TS690 and TS690ID can be configured to haveup to three parts set modes (Part Set A, Part Set Band Part Set C). This optio
Log Event Codes45TS690 & TS690ID Installation Manual Engineer's Menu 2LCD Starburst LED DescriptionAC OFFA.C. OFFPFMains power removed.AC RES
Log Event CodesReset User Code 1 [2.0]This option allows the installation engineer to resetthe master user (user 01) back to the factorydefault code o
Custom Text Menu (LCD Only) [2.B]This menu option allows the engineer to edit thefollowing text messages:Circuit TextThis option allows the engineer t
Modem PasswordThis option allows the modem password to beprogrammed. The “Modem Password” can be upto 16 character long and provides a means ofsecurit
Digicom TestsThis option allows the engineer to test eachchannel on the plug-on digi-modem (DC6) andthe five digi outputs on the main PCB.Reset Digi-M
5TS690 & TS690ID Installation Manual OverviewPrinterPrinterSpeakerSpeakerAux 12VAux 12VDCI ConnectionDCI ConnectionBell outputBell outputStrobeStr
Text Editing KeysWhen programming any text the keys on thekeypad function as shown below:1A2E3I4O5U60 (Zero)7Cursor left8N/U9Cursor right[Accept text0
AppendicesContact ID Extended ReportingContact ID extended reporting is a new formatwhich when used with the DC6 can be used toreport circuit ID data,
52Appendices TS690 & TS690ID Installation ManualPPPPPCCCCCCCPCPRKRKRKKey:10987621354Bedroom 1Bedroom 2BathroomLandingBedroom 3LoungeGarageKitchenD
Part-Set Application ExampleThis application example shows how to configurethe part set buttons to set different areas of a 3bedroom house.Using the d
Setup New UsersThe TS690 and TS690ID allows up to 15 users tooperate the alarm system, each user is assigned auser type and 4 digit passcode. User 01
Quick Reference Engineers MenusEngineers Menu 1key Options Page1Program Panel Outputs1 = Panel Output 1 (relay)2 = Panel Output 2 (-ve)3 = Panel Outpu
Quick Reference Engineers MenusEngineers Menu 2key Options Page1View CircuitsA = Scroll Next CircuitC = Scroll Previous Circuit422Set System TimeEnter
Quick Reference User MenusUser Menu 1key Options1Bell Test2Walk Test3Remote ResetEnter Reply code + ENT4Change Passcode (user)Enter new passcode5Enabl
59TS690 & TS690ID Installation Manual Notes
System ArchitectureSpecificationsControl PanelPart No.: TS690 - 6 to 14 zonesTS690M - with DC6 modemTS690ID - 2 to 38 zonesTS690IDM - with DC6 modemIn
496804 Issue 160Appendices TS690 & TS690ID Installation ManualCooper Security Ltd, Security House,Vantage Point Business Village,Mitcheldean, Glou
System InstallationCable RoutingWhen installing cables, the following should benoted:Ensure that all Network and detectioncircuit cables are kept clea
ID Loop Wiring (TS690ID Only)Each ID device is connected across a two-wire IDloop. Apart from observing the correct polarity,any wiring configuration
Control Panel InstallationProceed as follows:1. Open the control panel by removing twoscrews from the front cover. Remove the coverand disconnect the