Cooper TS690 Manuel d'installation

Naviguer en ligne ou télécharger Manuel d'installation pour Systèmes de contrôle d'accès de sécurité Cooper TS690. Cooper TS690 Installation manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 60
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
TS690 & TS690ID
Intruder Alarm Control Panels
Installation & Programming
Manual
_
~
Engineers menu 2
Select option :-
_
~
OPEN
_
~
Engineers menu 2
Select option :-
_
~
_
~
OPEN
1A
D
C
B
23
7
6
5
4
89
0
ENT
ESC
_
~
SYSTEM OPEN
17:30 01 Jan
SIL EN TZONE OMIT
CHIMENEW COD E 24 Hr OMIT
WALKTESTBELLTESTPart Set
Part Set
Part Set
RE SET
1
A
B
C
D
23
456
7
ENT ESC
8
0
9
Sett ing the Syst em
Enter your pa sscode XXXX
th en l ea ve the pro tect ed a rea.
Unsetting the System
Go directly to the keypad and
en ter you r p assc od e XXXX .
Resetting
Enter your pa sscode XXXX followed
by ENT then 3. Te leph on e yo ur a larm
com pan y and follo w their instr uct io ns.
!
See User Manual
FULL SET
Vue de la page 0
1 2 3 4 5 6 ... 59 60

Résumé du contenu

Page 1 - TS690 & TS690ID

TS690 & TS690IDIntruder Alarm Control PanelsInstallation & ProgrammingManual_~Engineers menu 2Select option :-_~OPEN_~Engineers menu 2Select o

Page 2 - Engineer’s Menu 1

Control Panel PCB Layout10System Installation TS690 & TS690ID Installation ManualPRINTERREMOTE KEYPADJP3DIGI-MODEMPLUG ON DIGI MODEMJP4FACTORYRESE

Page 3 - Appendices

Connection Terminals & IndicatorsConnection terminals on the TS690 / TS690ID aredescribed as ether “Safety Extra-Low Voltage”(SELV) circuits or “T

Page 4

Mains ConnectionThe mains supply is connected to a 3 way “EuroType” fused terminal block, which is fitted with a315mA fuse. All electrical connections

Page 5 - Number of Zones = 2 to 38

8 Network Connections & O/P.Terminals A to E are used to connect theremote keypad to the control panelnetwork. The O/P terminal is theprogrammable

Page 6 - Supply: 230V ±10% 50Hz

5. Set the “ENT KEY DISABLE” jumper link to therequired position.6. Set the “WARD SOUNDER CONTROL” jumper linkto the required position.7. Finally clip

Page 7

4. Connect “Remote Network” cables anddetection circuit cables to the appropriateterminals, see Figure 105. Set the I/D selector jumper link to the re

Page 8 - Cabling Requirements

Wiring ID BiscuitsEach ID biscuit is identified by its own number, 01to 30 and contains its own internal sensor which iscontinuously monitored by the

Page 9 - Control Panel Installation

Wiring a Biscuit to a Panic ButtonThe figure below shows typical wiring configurationfor a standard panic button.Wiring a Biscuit to a Smoke DetectorT

Page 10 - Control Panel PCB Layout

Extension LoudspeakersUp to two extension loudspeakers can beconnected across the [SPK+] and [H/O-] terminalson the control panel PCB. The volume for

Page 11

ApplicationThe DC6 digital communicator/modem is suitablefor connection to the following types of telephoneline:lDirect exchange lines (PSTN) supporti

Page 12 - FUSE 315mA

ContentsOverviewIntroduction . . . . . . . . . . . . . . . . . . . . . . . . . 4Control Panel . . . . . . . . . . . . . . . . . . . . . . . . 4Remote

Page 13 - Installation Procedure

InstallationFor your safety, installation of the DC6MUST be carried out in the sequenceshown below:1. Ensure that all power is removed from thesystem

Page 14 - TS700 LEC Installation

Connecting a PrinterThe TS690 and TS690ID supports two type ofprinters, the CPA6 printer (no longer available) andany standard RS232 printer. When usi

Page 15 - End Of Line

Pre Power-Up ChecksOnce the system is installed, but prior topowering-up, give the system one final check toensure that:1. The wiring conforms to the

Page 16 - Wiring A Biscuit to a PIR

3. With the ID loop still disconnected from thecontrol panel, use a DVM to measure theresistance between the following cores andterminals:(a) ID + cor

Page 17 - Auxiliary Tamper

NVM Defaults24System Installation TS690 & TS690ID Installation ManualSection Option DefaultUser CodesUser 00 Engineer 1234User 01 Master 5678Panel

Page 18 - Regulatory Requirements

Engineer’s Menu 1IntroductionEngineers menu 1 is the first of two engineersmenus, which is selected when the engineer’spasscode is entered. The engine

Page 19 - Connections

Panel Outputs [1.1]Outputs 1-3 on the control panel and remotekeypad outputs 5-8 can be programmed to anyof the output types shown on pages 26 to 29.D

Page 20 - DC54 & DC58M Installation

No Type/Description004 Walk TestActivates when the "Walk Test" option isselected and deactivates when the "Walk Test"option is fin

Page 21 - RS232 Data

No Type/Description032 Duress AlarmActivates when a duress passcode is enteredand deactivates when the duress alarm isreset.033 System Part SetActivat

Page 22 - Pre Power-Up Checks

and the circuit remains active until the end ofthe confirmation time then the control panelomits the active zone and triggers the ActiveOmit output. T

Page 23 - Power-Up Checks

Add/Clear ID Devices (TS690ID) . . . . . . . . . . 39Clear & Relearn ID Devices . . . . . . . . . . . 39Add ID Devices. . . . . . . . . . . . . .

Page 24 - NVM Defaults

[7] Inverted - Inverts the operation of thekeyswitch.If the “Keyswitch” is not assigned to any of theabove options, the circuit becomes a“Monitored” c

Page 25

System Timers [1.5]The system timers are as follows:00 Abort DelayThis timer sets the period in which the alarmsignal may be aborted following an alar

Page 26 - Programmable Output Types

06 Bell DurationThis controls the duration of the externalbell/sounder. If the timer is set to 199 the belloutput is continuous. This timer has a work

Page 27 - No Type/Description

19 Test CallIf the system is fitted with a DC6, it is possible forthe control panel to make the DC6 send atimed test call to the central station. The

Page 28

To set the system the user first enters theiraccess code at a keypad or operates akeyswitch. The control unit starts the exit tone.Note that the exit

Page 29 - Circuit Types

Remote Reset Algorithm [1.8]When the system is programmed for “EngineerReset” the requirement to send an engineer to sitecan be overridden by the user

Page 30 - Circuit Attributes

10 Tamp user resetWhen programmed as “Yes", tamper alarmscan be reset by the user. When programmedas ”No", tamper alarms can only be reset b

Page 31 - System Timers [1.5]

25 Answer Phone DefWhen programmed as “Yes”, the plug-ondigi-modem will only answer incoming callsafter a second attempt. When programmedas “No”, the

Page 32

34 Entry Keypad LockWhen programmed as “Yes” then users cannotunset the system from a keypad during entry.Program this option as “Yes” if you are inst

Page 33 - Setting Modes [1.6]

Go to User Menu 1 [1.0]This option allows the engineer to access “Usermenu 1", the flowchart below shows the optionswithin ”User menu 1", fo

Page 34 - Do System Print [1.7]

OverviewIntroductionThe TS690 range of alarm control systems havebeen designed to suit small to medium installationsites. The TS690 system can monitor

Page 35 - Configuration [1.9]

View Location Text (LCD Only) [1.B]This option allows the engineer to view the panellocation text. The text message is programmed in"Engineers me

Page 36

Engineer's Menu 2IntroductionEngineer's menu 2 is selected by pressing the [ENT]key whilst Engineer's menu 1 is selected. Eachmenu opti

Page 37

View Circuits [2.1]Each detection circuit may be viewed toascertain its status. The circuit status conditionsand resistance are shown below:Status Res

Page 38 - 38 Keypad PA On

Change Passcode [2.4]This option allows the engineer to change theirpasscode. The default passcode is 1234 but theinstallation engineer should change

Page 39 - HIGH 9.0 to 10.1V

Configure Part Sets [2.8]The TS690 and TS690ID can be configured to haveup to three parts set modes (Part Set A, Part Set Band Part Set C). This optio

Page 40 - Relearn Hardware [1.C]

Log Event Codes45TS690 & TS690ID Installation Manual Engineer's Menu 2LCD Starburst LED DescriptionAC OFFA.C. OFFPFMains power removed.AC RES

Page 41

Log Event CodesReset User Code 1 [2.0]This option allows the installation engineer to resetthe master user (user 01) back to the factorydefault code o

Page 42 - StarburstLCD

Custom Text Menu (LCD Only) [2.B]This menu option allows the engineer to edit thefollowing text messages:Circuit TextThis option allows the engineer t

Page 43 - Print System Log [2.7]

Modem PasswordThis option allows the modem password to beprogrammed. The “Modem Password” can be upto 16 character long and provides a means ofsecurit

Page 44 - View System Log [2.9]

Digicom TestsThis option allows the engineer to test eachchannel on the plug-on digi-modem (DC6) andthe five digi outputs on the main PCB.Reset Digi-M

Page 45 - Log Event Codes

5TS690 & TS690ID Installation Manual OverviewPrinterPrinterSpeakerSpeakerAux 12VAux 12VDCI ConnectionDCI ConnectionBell outputBell outputStrobeStr

Page 46 - Start Call Back [2.A]

Text Editing KeysWhen programming any text the keys on thekeypad function as shown below:1A2E3I4O5U60 (Zero)7Cursor left8N/U9Cursor right[Accept text0

Page 47 - LCD Only

AppendicesContact ID Extended ReportingContact ID extended reporting is a new formatwhich when used with the DC6 can be used toreport circuit ID data,

Page 48 - Program Digicom

52Appendices TS690 & TS690ID Installation ManualPPPPPCCCCCCCPCPRKRKRKKey:10987621354Bedroom 1Bedroom 2BathroomLandingBedroom 3LoungeGarageKitchenD

Page 49

Part-Set Application ExampleThis application example shows how to configurethe part set buttons to set different areas of a 3bedroom house.Using the d

Page 50 - Common Key Sequences

Setup New UsersThe TS690 and TS690ID allows up to 15 users tooperate the alarm system, each user is assigned auser type and 4 digit passcode. User 01

Page 51

Quick Reference Engineers MenusEngineers Menu 1key Options Page1Program Panel Outputs1 = Panel Output 1 (relay)2 = Panel Output 2 (-ve)3 = Panel Outpu

Page 52

Quick Reference Engineers MenusEngineers Menu 2key Options Page1View CircuitsA = Scroll Next CircuitC = Scroll Previous Circuit422Set System TimeEnter

Page 53 - TS690/TS690ID

Quick Reference User MenusUser Menu 1key Options1Bell Test2Walk Test3Remote ResetEnter Reply code + ENT4Change Passcode (user)Enter new passcode5Enabl

Page 55 - Engineers Menu 1

59TS690 & TS690ID Installation Manual Notes

Page 56 - Output Types

System ArchitectureSpecificationsControl PanelPart No.: TS690 - 6 to 14 zonesTS690M - with DC6 modemTS690ID - 2 to 38 zonesTS690IDM - with DC6 modemIn

Page 57 - User Menu 2

496804 Issue 160Appendices TS690 & TS690ID Installation ManualCooper Security Ltd, Security House,Vantage Point Business Village,Mitcheldean, Glou

Page 58

System InstallationCable RoutingWhen installing cables, the following should benoted:Ensure that all Network and detectioncircuit cables are kept clea

Page 59

ID Loop Wiring (TS690ID Only)Each ID device is connected across a two-wire IDloop. Apart from observing the correct polarity,any wiring configuration

Page 60 - 496804 Issue 1

Control Panel InstallationProceed as follows:1. Open the control panel by removing twoscrews from the front cover. Remove the coverand disconnect the

Commentaires sur ces manuels